Descargar Imprimir esta página

Siemens 3RW4900-0KC00 Instructivo página 8

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
2.2 Activating the PROFIBUS communication module via the device interface with the "Soft Starter ES
Professional" software
Perform the following steps in order to activate the communication module:
1. Connect the 3RW44 soft starter via the interface cable with a PC on which the "Soft Starter ES Professional" software is installed.
2. Start the "Soft Starter ES Professional" software.
3. Select "Switching Device > Open online" in the menu.
4. Select the option "local device interface"in the "Open online" dialog and select the desired COM port under "interface".
5. Click on "OK".
6. Select "Device configuration" in the left-hand window area.
7. Activate the "Fieldbus interface" check box in the right-hand window area.
8. Select "Device parameters > Fieldbus" in the left-hand window area.
8