Modbus: Parameter Overview - Wilo Control SC-Booster Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 259
English

13.4 Modbus: Parameter overview

Holding
Name
register
40001
Communication profile
(0)
version
40002
Wink service
(1)
40003
Switchgear type
(2)
40008 –
Switchgear data ID
40009
(7 – 8)
40014
BusCommand timer
(13)
40015
Drives on/off
(14)
40026
Actual value
(25)
40027
Current setpoint
(26)
40028
Number of pumps
(27)
40029
Maximum number of
(28)
active pumps
40033
Pump status 1
(32)
40034
Pump status 2
(33)
50
Data type
Scaling
and unit
UINT16
0.001
BOOL
ENUM
UINT32
ENUM
BOOL
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1/day
1/month
0.1 psi
UINT16
UINT16
BITMAP
BITMAP
Elements
0. SC
1. SC...FC
2. SCe
3. CC
4. CC...FC
5. CCe
6. SCe NWB
7. CCe NWB
8. EC
9. ECe
10. ECe NWB
0. –
1. Off
2. Set
3. Active
4. Reset
5. Manual
0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
Access
Added
R
31,000
RW
31,000
R
31,000
R
31,000
RW
31,000
RW
31,000
R
31,000
RW
31,000
R (dp-v)
R (dT-v)
R
31,000
R
31,000
R
31,000
R
31,000
WILO SE 09/2018

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Control sc-fc-boosterControl sce-booster

Tabla de contenido