Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe)
Description
The absolute pressure setpoint in the event of zero
flow. This value is automatically calculated based on
the relative setpoint in the event of zero flow.
The menu for the pressure thresholds for the
activation and deactivation of pumps
The threshold for activation of the base-load pump
relative to the active setpoint
The absolute threshold for activation of the base-
load pump. This value is automatically calculated
based on the relative threshold and the current
setpoint.
The threshold for switching off the base-load pump
relative to the active setpoint
The absolute threshold for switching off the base-
load pump. This value is automatically calculated
based on the relative threshold and the current
setpoint.
The threshold for activation of the first peak-load
pump relative to the active setpoint
The absolute threshold for activation of the first
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
English
Parameter range
Factory setting
0 ... setpoint at Q
max
75 ... 90 ...100
100... 105 ... 125
75 ... 90 ...100
17