ABB ACH580-34 Manual Del Usuario página 15

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29
terminals as possible. Twisting the wire with its return wire reduces disturbances
caused by inductive coupling.
7. Install the middle front cover back.
Default I/O connection diagram (HVAC default configuration)
1...10 kohm
max.
500 ohm
6)
4)
5)
Damper actuator
Run status
Fault status
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V
DC).
Digital inputs DI1...DI5 also support 10 to 24 V AC
Terminal sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference: 0...10 V
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Actual feedback: 0...20 mA
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0...10 V
8
AO2
Motor current: 0...20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Not configured
15
DI3
Constant frequency/speed selection
16
DI4
Start interlock 1 (1 = allow start)
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
Embedded fieldbus, EFB (EIA-485)
30
A-
31
DGND
S4
TERM
Termination switch
S5
BIAS
Bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off (STO). Both circuits must be closed for
35
OUT2
the drive to start. The drawing shows the simplified
36
SGND
connection of an emergency stop button through a safety
relay (K). If STO is not used, leave the factory-installed
37
IN1
jumpers in place. See also section Safe torque off (STO).
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.
41
24 V AC/DC- in
2
(all terminals)
EN – Quick installation guide 15
1)
Damper control
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
1)
EN
2)
DA
3)
DE
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Acs880-34

Tabla de contenido