OMNIA ST 3.2
TBH - Electrical heater for DHW boiler
16
13
CN11
Power supply
A1
A2
TCO
ATCO
H-L1-C - For room thermostat (high voltage)
There are three methods for connecting the thermostat.
•
Room thermostat method A (mode set control)
To activate this function set the service parameter 6.1 "Room thermostat" = 1
(mode setting) refer "9.2 Service parameters table" on page 117.
A.1 When unit detect voltage is 230VAC between C and L1 ,the unit operates in
the cooling mode.
A.2 When unit detect voltage is 230VAC between H and L1, the unit operates in
the heating mode.
A.3 When unit detect voltage is 0VAC for both side(C-L1, H-L1) the unit stop wor-
king for space heating or cooling.
A.4 When unit detect voltage is 230VAC for both side(C-L1, H-L1) the unit working
in cooling mode.
3 4
15
CN11
3
15
4
HEAT(H)
L1
COOL(C)
POWER
IN
RT1
25 26
27
28
1 2 3 4 5
29 30 31 32
6 7 8 9 10
CN7
CN30
(TBH)
fig. 28 -
25 26
27 28
1 2 3 4 5
29 30 31 32
6 7 8 9 10
CN7
CN30
Method A
(Mode set control)
fig. 29 -
Cod. 3541V991 - Rev. 00 - 09/2021
•
Room thermostat method B (one zone control)
To activate this function set the service parameter 6.1 "Room thermostat" = 2 (one
zone) refer "9.2 Service parameters table" on page 117.
B.1 When unit detect voltage is 230VAC between H and L1, unit turns on.
B.2 When unit detect voltage is 0VAC between H and L1, unit turns off.
3
15
CN11
HEAT(H)
L1
POWER
IN
RT1
•
Room thermostat method C (double zone control))
To activate this function set the service parameter 6.1 "Room thermostat" = 3
(double zone) refer "9.2 Service parameters table" on page 117.
C.1 When unit detect voltage is 230VAC between H and L1,zone1 turns on.When
unit detect voltage is 0VAC between H and L1, zone1 turns off.
C.2 When unit detect voltage is 230VAC between C and L1, zone2 turns on ac-
cording to climate temp curve. When unit detect voltage is 0V between C and L1,
zone2 turns off.
C.3 When H-L1 and C-L1 are detected as 0VAC, unit turns off.
C.4 when H-L1 and C-L1 are detected as 230VAC, both zone1 and zone2 turn on.
3 4
15
S1
CN4
L1
HEAT(H)
POWER IN
RT1
zone1
25 26
27 28
1 2 3 4 5
29 30 31 32
6 7 8 9 10
CN7
CN30
Method B
(One zone control)
fig. 30 -
25 26
27 28
1 2 3 4 5
29 30 31 32
6 7 8 9 10
CN11
CN7
CN30
Method C
(Double zone control)
COOL(C)
POWER IN
RT2
zone2
fig. 31 -
EN
103