Use only the suitable box wrench provided for
this operation to remove the nozzle, taking
care to not damage the electrodes. Fit the new
nozzle with the same care.
Note: Always check the position of electrodes
after having replaced the nozzle (see illustra-
tion). A wrong position could cause ignition
troubles.
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 μA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 μA.
The adjustment of the com-
bustion head position is car-
ried out in order to
obtain the best combustion
efficiency. When installed for
small output operations,
the head shall be adjusted back.
For maximum operation the position is fully forward.
Steps: loosen the locking screw of A lever. Move the lever to
the needed position. Tighten back the locking screw.
8
I
0
NOZZLE CLEANING AND REPLACEMENT
FLAME DETECTOR SYSTEM CHECK
ADJUSTING THE FIRING HEAD
2
0
1
DESCRIPTION OF CONTROL PANEL
1
1 - Fuse
2
2 - Termal lock-out lamp
2
0
1
7
3 - Light-oil working lamp
3
4 - Gas working lamp
4
5 - High-low flame switch
5
6 - Main switch I / O
6
7 - Gas/Light-oil selector switch:
1- Light-oil operation
2- Gas operation
8 - Lockout disable push button
3÷4 mm
2 fiamme
min.
max.
A
MULTICALOR
45-70-100
REMOVING THE BLAST TUBE
I - Manual low flame position
II
Manual operation : high flame position
-
Automatic operation : HI-LOW flame position by
the HI-LOW thermostat.
18
5÷6 mm
SW
BL
BL
SW
SW = BLACK
BL = BLU
min.
A
MULTICALOR
140
2
0
Pull up the switch on the ter-
minal strip to keep burner in
first stage.
1
LGB 22
2
QRA
max.
1