Light-Oil Circuit; Priming And Adjustment Of Oil Pump - Ecoflam Multicalor 45 Manual De Instrucciones

Ocultar thumbs Ver también para Multicalor 45:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29
A - HOSE
B - OIL FILTER
C - OIL COCK
1 - PUMP
2 - SAFETY OIL VALVE
3 - LOW FLAME OIL VALVE
4 - HIGH FLAME OIL VALVE
5 - LOW FLAME NOZZLE
6 - HIGH FLAME NOZZLE
7 - GAS PRESSURE SWITCH
8 - SAFETY GAS VALVE
9 - LOW FLAME GAS VALVE
10 - HIGH FLAME GAS VALVE
A
A
B
SUNTEC AS 67 ...
SUNTEC AS 67 B
4
3
6
5
V
P
SUNTEC
SUNTEC
3
3
2
1
The pump is adjusted during testing and inspection to
12 bar. VERIFY: - That piping system is perfectly sealed; - That the use of
hoses is avoided whenever is possible (use copper pipes preferably); - That
depression is not greater than 0,45 bar, to avoid pump's cavitation; - That
check valve is suitably designed for the duty; The pump pressure is set at a
value of 12 bar during the testing of burners. Before starting the burner,
bleed the air in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming. Start the
burner and check the pump feeding pressure. In case the pump priming does not take place during the first prepurging,
with a consequent, subsequent lock-out of the burner, rearm the burner's lock-out to restart, by pushing the button on
the control box. If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure
drop in the pump, rearm the burner's lock-out to restart the burner. Do not allow the pump to work without oil for
more than three minutes. NOTE: Before starting the burner, check that the return pipe is open. An eventual
obstruction could damage the pump sealing device.

LIGHT-OIL CIRCUIT

SUCTION
RETURN
SUCTION
RETURN
C

PRIMING AND ADJUSTMENT OF OIL PUMP

SUNTEC AN 77
3
6
P
V
SUNTEC
SUNTEC
3
2
1
VgS
1
2
° STADIO GASOLIO
VGS
7
8
VgS
1
2
° STADIO GASOLIO
VGS
8
7
SUNTEC AJ 6 C-C
3
4
5
5
SUNTEC
SUNTEC
3
4
2
1
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
17
420010350301 Multicalor 45 ÷ 140
Vg1
5
3
Vg2
4
VG1
6
10
VG2
9
Vg1
5
3
Vg2
4
VG1
6
10
VG2
9
SUNTEC D 67 A
6
6
SUNTEC
SUNTEC
SUNTEC
3
1
2
EN
5
4
3