Concealed Duct High Static Pressure
10
AIR CONDITIONER OPERATIONS AND
PERFORMANCE
3 minutes protection function
3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit
breaker is turned on for re-starting the air conditioner.
Power failure
Power failure during operation will stop the unit completely.
• To restart the operation, push the ON/OFF button on the remote controller.
• Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main power switch or
circuit breaker and then turn them on again. Push the ON/OFF button on the remote controller to restart.
Heating characteristics
Preheating operation
The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out after approximately
5 minutes when the indoor heat exchanger warmed up.
Warm air control (In heating operation)
When the room temperature has reached the set temperature while the outdoor unit is stopping, the indoor unit discharges wind
with a very small air volume.
Defrosting operation
If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately 2 to 10 minutes) to
maintain the heating capacity.
• The fans in both indoor and outdoor units will stop during the defrosting operation.
• During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor unit.
Heating capacity
In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating is called heat
pump system. When the outside temperature is too low, it is recommended to use another heating apparatus in combination
with the air conditioner.
Attention to snowfall and freeze on the outdoor unit
• In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up.
If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.
• In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside for freeze
prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine failure or poor warming.
Air conditioner operating conditions
For proper performance, operate the air conditioner under the following temperature conditions:
Cooling operation
Heating operation
If air conditioner is used outside of the above conditions, safety protection may work.
19-EN
Outdoor temperature
: –15°C to 46°C
Room temperature
: 21°C to 32°C (Dry bulb temp.), 15°C to 24°C (Wet bulb temp.)
Room relative humidity – less than 80 %. If the air conditioner operates in excess of this
[CAUTION]
figure, the surface of the air conditioner may cause dewing.
Outdoor temperature
: –20°C to 15°C (Wet bulb temp.)
Room temperature
: 15°C to 28°C (Dry bulb temp.)
– 19 –
Owner's Manual