3.8
WATER FLOW
GUAGE
The water flow gauge (8 fig. 4) intervenes,
blocking burner functioning, if it detects
that there is insufficient water circulating in
the primary circuit (< 450 l/h).
To res t ore burner functioning, check
600
500
400
300
200
100
0
600
500
400
300
200
100
0
system pressure and the functioning of the
pump and the flow switch, and the cleaning
of the "Aqua Guard Filter System" filter.
N.B.: when replacing the flow meter valve,
verify that the arrow printed on its body
is pointing in the same direction of the
water flow.
200
400
600
12 BFT - 12 SYSTEM
200
400
600
PORTATA (l/h)
By-pass on
By-pass inserito
con by-pass
By-pass on
senza by-pass
By-pass off
35 BF - TOP 35 BF
30 BF - TOP 30 BF
25 BF - TOP 25 BF
800
1000
PORTATA (l/h)
FLOW RATE (l/h)
con by-pass
By-pass on
senza by-pass
By-pass off
35 BFT - TOP 30 BFT - 35 SYSTEM
30 BFT - TOP 25 BFT - 30 SYSTEM
20/25 BFT - 20 SYSTEM
800
1000
FLOW RATE (l/h)
By-pass off
By-pass escluso
3.9
HEAD AVAILABLE TO SYSTEM
Residual head for the heating system is
shown as a function of rate of flow in the
graph in fig. 14.
To obtain the maximum head available to
the system, turn off the by-pass by turning
the union to the vertical position (fig. 15).
1200
1200
Fig. 14
Fig. 15
ES
PT
GB
89