• When leaf 1 arrives at the desired opening position
• When leaf 2 arrives at the desired opening position
• Counting of the pause time in opening starts
• When the desired pause time has elapsed
Leaf 1 starts closing. (phase shift time setting)
• START
• When leaf 2 arrives at the closing position
• When leaf 1 arrives at the closing position
• Now the procedure is over, the menu C21 reappears blinking (without Y)
• If you want to repeat the operation, press OK
• If you want to finish the times learning operation and save the data, press ESC as long as the horizontal lines appear on the display
WARNING:
During the times self-learning phase, motion always occurs at a non-decelerated speed.
If decelerations are needed, stop the leaves before the stroke, then remember to enable the decelerations option
(menu C6) and set the decelerations times (menu H3 and H6).
During the times self-learning phase, the limit switches and the amperometric thresholds are not considered.
The microcontroller does not consider fractions of times of less than 1 second, so the real time is rounded up or
down.
The times set following this procedure can be modified later by entering the proper menus and modifying the
numeric value.
If the instalment is configured as double sliding, the motors will move as indicated in the procedure with the
phase shift in opening and closing.
During normal working, phase shifts are zeroed.
USING THE LIMIT SWITCHES
If the deceleration function is enabled, the limit switches mark the start of the deceleration time. The gate
continues the decelerated motion for the time set in menus H3 and H6.
If 2 limit switches are used, the first one starts the deceleration and the second one ends it.
The deceleration, if enabled, will start upon reaching the limit switches and will last for the time H3 and H6 until
the second limit switch has been reached, ending the deceleration phase.
Make sure that the times set are higher than the time necessary to reach the limit switch.
If deceleration is not enabled, the limit switches lock the motion.
The additional time T3 and the final opening/closing stroke, if enabled, work even when there are limit switches.
RESET
The simultaneous pressure of the + and – keys for 3 seconds when the writing PASS is displayed will reset all
values, and the default settings will be loaded (only the number of performed cycles are still stored).
FLASHING LIGHT SIGNALS SUMMARY
Device
Photo 2 intercepted in stand-by after a
start command
Edge intercepted in stand-by after a
start command
Edge intercepted in pause after a start
command or at closing
START
leaf 1 stops
START
leaf 2 stops
START
leaf 2 starts closing
START
·leaf 2 stops
START
·leaf 1 stops
Signal
5 fast flashings
3 slow flashings
3 fast flashes
UK
Effect
When released, it opens
Blocked closed door
Blocked open door
39