Siemens 7LF4 542-0 Instrucciones De Operación página 24

Programador estacional expert de 2 canales y gps
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 58
Offset - B
* This function is available in Expert mode.
Setting the correction value (1...30 min.) extends the daily ON
period in the middle of the winter season by up to 60 minutes
(OFF up to 30 min. later in the morning, ON up to 30 min.
earlier in the evening).
In the middle of the summer season, the correction setting
reduces the daily ON period by up to 60 minutes (OFF up to 30
min. earlier in the morning, ON up to 30 min. later in the
evening).
h
21.03.
24
22
20
18
16
Switching-point
14
Offset
12
Correction
10
8
6
4
2
0
0
30
60
90
120
150 180
24
2514264126-02
3ZW1012-7LF45-0AA0
23.09
210
240
270
300
330
360
d
t
0h
3
6
9
12
1
0
max. 120min
The time switch switches on at the calculated sunset time and off at the
calculated sunrise time.
By setting an offset, you can shift the switching times by up to ±120
minutes with respect to the calculated sunrise and sunset times.
Example:
If you set the offset to +30 minutes, the time switch will switch 30
minutes after sunrise and 30 minutes after sunset. If you set the offset to
-30 minutes, the time switch will switch 30 minutes before sunrise and
30 minutes before sunset.
0h
3
6
9
-50'
1
0
If the offset setting is in degrees the time switch switches on and off at
times of equal brightness, despite the differences in twilight time
lengths over the course of the year.
Sunrise and sunset correspond to -50' for the centre of the sun (the edge
of the sun is visible on the horizon).
15
18
21
24h
max. 120min
12
15
18
21
24h