8. CONDENSATE HOSE CONNECTION
Drain hose connection
1. Use standard hard PVC pipe for the drain pipe.
2. Use the drain hose (Prepared on site)to change the direction.
3.
Insert the drain hose until it connects the drain port very well, and then secure it tightly with
the hose clamp(Prepared on site)( Fig.12)
4.
After checking the drainage, wrap the drain hose with the insulation and clamp.
(Prepared on site)( Fig.12)
Drain port
OD:31.2mm(Model 24-48)
OD:25mm(Model 09-18)
Fig.12
Caution!
1. Do not raise the drain pipe higher than 0.75m, or else there will be water leak risk.
2. Make sure the drain pipe has a downward gradient (no less than 1/100) and there are no
water traps (Fig.13).
3. To hold the drain pipe, space bracket every 1 to 1.5m.(Fig.13)
Drain hose
(Prepared on site)
Clamp (Prepared on site)
Fig.13
Drain clamp (Accessory)
Drain hose (Accessory)
Insulatio(Accessory)
Ceiling
14
Indoor unit cassette type
Hard PVC pipe
Connected by hose connector
(Prepared on site)
Hard PVC pipe
Bracket
1 1.5m
0.75m
1/100 gradient or more