4.4.3

Branch circuit protection

Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
AC 400/500 V devices
Three Phase 380 V – 500 V Voltage Range
SCCR: 200 kA/ 500 V
when protected by:
Model
Non Semiconductor Fu-
ses (currents are maxi-
mum values)
®
MOVIDRIVE
MODEL,
15 A / 600 V
0005 (Size 0S)
®
MOVIDRIVE
MODEL,
15 A / 600 V
0008 (Size 0S)
®
MOVIDRIVE
MODEL,
15 A / 600 V
0011 (Size 0M)
®
MOVIDRIVE
MODEL,
15 A / 600 V
0014 (Size 0M)
®
MOVIDRIVE
MODEL,
35 A / 600 V
0015 (Size 1)
®
MOVIDRIVE
MODEL,
35 A / 600 V
0022 (Size 1)
®
MOVIDRIVE
MODEL,
35 A / 600 V
0030 (Size 1)
®
MOVIDRIVE
MODEL,
35 A / 600 V
0040 (Size 1)
®
MOVIDRIVE
MODEL,
60 A / 600 V
0055 (Size 2S)
®
MOVIDRIVE
MODEL,
60 A / 600 V
0075 (Size 2S)
®
MOVIDRIVE
MODEL,
60 A / 600 V
0110 (Size 2)
®
MOVIDRIVE
MODEL,
175 A / 600 V
0150 (Size 3)
®
MOVIDRIVE
MODEL,
175 A / 600 V
0220 (Size 3)
®
MOVIDRIVE
MODEL,
175 A / 600 V
0300 (Size 3)
®
MOVIDRIVE
MODEL,
350 A / 600 V
0370 (Size 4)
®
MOVIDRIVE
MODEL,
350 A / 600 V
0450 (Size 4)
®
MOVIDRIVE
MODEL,
225 A / 600 V
0550 (Size 5)
®
MOVIDRIVE
MODEL,
225 A / 600 V
0750 (Size 5)
®
MOVIDRIVE
MODEL,
250 A / 600 V
0900 (Size 6)
SCCR: 200 kA/ 500 V
SCCR: 65 kA/ 480 V:
when protected by
when protected by
Inverse-Time Circuit
Type E Combination Motor Controller
Breaker (currents are
maximum values)
25 A/ 500 V
ABB, Model MS132-2.5
Rated 480 V, 1 HP
25 A / 500 V
ABB, Model MS132-4.0
Rated 480 V, 2 HP
25 A / 500 V
ABB, Model MS132-4.0
Rated 480 V, 2 HP
25 A / 500 V
ABB, Model MS132-6.3
Rated 480 V, 3 HP
25 A / 500 V
ABB, Model MS132-6.3
Rated 480 V, 3 HP
25 A / 500 V
ABB, Model MS132-6.3
Rated 480 V, 3 HP
25 A / 500 V
ABB, Model MS132-10
Rated 480 V, 5 HP
25 A / 500 V
ABB, Model MS132-12
Rated 480 V, 7.5 HP
25 A / 500 V
ABB, Model MS132-16
Rated 480 V, 10 HP
25 A / 500 V
ABB, Model MS132-20
Rated 480 V, 10 HP
-
ABB, Model MS132-32
Rated 480 V, 20 HP
90 A / 500 V
ABB, Model MS450-40E
Rated 480 V, 30 HP
90 A / 500 V
ABB, Model MS495-63E
Rated 480 V, 50 HP
90 A / 500 V
ABB, Model MS495-75E
Rated 480 V, 60 HP
175 A / 500 V
ABB, Model MS495-90E
Rated 480 V, 75 HP
175 A / 500 V
-
175 A / 500 V
-
175 A / 500 V
-
300 A / 500 V
-
Instrucciones de funcionamiento – MOVIDRIVE
Instalación
Information regarding UL
SCCR: 65 kA/ 460 V
1)
:
when protected by:
Rockwell Automation Mo-
del 140M-C2E-B25, Rated
460 V, 1.5 HP
Rockwell Automation Mo-
del 140M-C2E-B40, Rated
460 V, 3 HP
Rockwell Automation Mo-
del 140M-C2E-B40, Rated
460 V, 3 HP
Rockwell Automation Mo-
del 140M-C2E-B63, Rated
460 V, 5 HP
Rockwell Automation Mo-
del 140M-C2E-B63, Rated
460 V, 5 HP
Rockwell Automation Mo-
del 140M-C2E-B63, Rated
460 V, 5 HP
Rockwell Automation Mo-
del 140M-C2E-C10, Ra-
ted 460 V, 7.5 HP
Rockwell Automation Mo-
del 140M-D8E-C16, Ra-
ted 460 V, 10 HP
Rockwell Automation Mo-
del 140M-D8E-C16, Ra-
ted 460 V, 10 HP
Rockwell Automation Mo-
del 140M- D8E-C20, Ra-
ted 460 V, 15 HP
Rockwell Automation Mo-
del 140M-F8E-C32, Rated
460 V, 25 HP
Rockwell Automation Mo-
del 140M-F8E-C45, Rated
460 V, 30 HP
-
-
-
-
-
-
-
®
MDX60B/61B
4
83

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Movidrive mdx61b serie

Tabla de contenido