EB TECHNOLOGY START-S2XL Instrucciones Y Advertencias Para El Instalador página 47

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.00 Turning on and learning of the control unit
If everything has been correctly connected, when turning on the red light of LED L1 TEST should flash,
while STOP, FOTO, FCA( opening Limit Switch), FCC (Closing Limit Switch) should lit up (if the gate is closed and if the closing
limit switch is connected, it should turned off) . LED START and PED (partial opening) are turned off.
The working time procedure is as follow. To execute such operation you can use START (open) or any device connected
to the terminal board 19-16 to open with START control or with a remote control ( previous memorized)
During the programming you can hear the relay even it is not connected, when opening it sounds fastly
(1-2 seconds) when closing it sounds slowly (1 second)
If the flashing light has been connected (terminal board no. 3-4-8-9),
it flashes fastly when opening ( 1-2 seconds) and slowly when closing ( 1 second).
5.01 Working time with or without limit switches
DIP B
1
2
4
3
1
Put in OFF the micro-switches 3 and 4 of the DIP B.
2
Power the control unit.
Push the control START ( everything connected to the input 16 or to
3
the first channel of the remote control ) from now it starts counting.
Push the button PULSANTE P1 and from now it memorize
4
the working time.
When the gate opens at the choosen point, press button
5
PULSANTE P1. If you use the limit switch you don't need to press P1.
6
Let the time goes for the opening time.
7
Press the button PULSANTE P1 to start closing.
8
Wait until the gate stops automatically. The gate is closed.
9
Program the dip for the personalized program again.
5.02 Time programming with limit switches
DIP B
1
2
3
4
As mentioned, if you need to personalized the pause time it is necessary to programm
as described in the chapter 5.01. Then to personalized the pause time see the chapter 4.01.
Turn off the control unit, close the gate,
put in OFF the terminal board no. 3 and 4 of DIPB
and power the control unit again.
Go forward with the personalized programming see previous chapter 4.01
When you use the limit switches you can use the standard working time of the control unit.
The programming can be activated with micro-switch 4 of DIP B.
Fixed working time up to 90 seconds. Fixed pause time up to 10 seconds.
The gate is closed
The gate is closed.
The gate opens, the relay sounds fastly.
The control unit counts.
The gate stops.
The gate is in PAUSE TIME:
The relay light stops.
The gate starts closing,
the relay sounds slowly.
The gate is closed.
Programming is over.