Technical Specifications
Dimensions (H x W x D):
Power supply:
Capacity, switching output 1:
(COM 1/COM 2)
Electronic ballast:
(COM 1/COM 1 AP/COM 2/DIM)
Capacity, switching output 2:
(COM 2 only)
Square detection zones:
Light-level setting:
Switching output 1:
Time setting
Switching output 2:
Time setting
DIM:
Time setting
Control output:
Installation height:
(mounted to ceiling)
Installation site:
Sensors:
IP rating:
Protection class:
Temperature range:
120 x 120 x 76 mm
230 – 240 V, 50 Hz / 60 Hz
230 V relay
resistive load of 2000 W max. (cos φ = 1)
1000 VA max. (cos φ = 0.5)
Max. 'ON' current 800 A/200 μs
30 x (1 x 18 W), 25 x (2 x 18 W)
25 x (1 x 36 W), 15 x (2 x 36 W)
20 x (1 x 58 W), 10 x (2 x 58 W)
Pay attention to specific 'ON' currents of electronic ballasts!
A relay or contactor must be provided on line side for higher
switching capacities.
Presence
max. of 230 W/230 V
1A max., (cos φ = 1) for HVAC (heating/ventilation/air conditioning)
IR Quattro
Presence: max. of 4 x 4 m (16 sq.m.)
Radially: max. of 5 x 5 m (25 sq.m.)
Tangentially: max. of 7 x 7 m (49 sq.m.)
10 – 1000 lux, ∞ / daylight /
DIM 100 – 1000 lux control threshold
30 sec. – 30 min., pulse mode (approx. 2 sec.),
IQ mode (automatic adjustment to the usage profile)
COM2 only, for HVAC
0 sec. – 10 min. switch-'ON' delay
1 min. – 2 hrs. stay-'ON' time
Automatic room surveillance
30 sec. – 30 min.,
IQ mode (automatic adjustment to the usage profile)
1 – 10 V / max. of 50 electronic ballasts, max. of 100 mA
2.5 m – 8 m (IR Quattro)
2.5 m – 10 m (IR Quattro HD)
indoors
13 detection levels, 1760 switching zones (IR Quattro)
13 detection levels, 4800 switching zones (IR Quattro HD)
IP 20
II
0° C to +40° C
- 23 -
IR Quattro HD
max. of 8 x 8 m (64 sq.m.)
max. of 8 x 8 m (64 sq.m.)
max. of 20 x 20 m (400 sq.m.):