Step 4: (ELECTRIC DRYER ONLY)
Connect Electrical Plug
For further assistance, refer to Section on Electrical
Requirements.
IMPORTANT: Use only a new U.L. listed No. 10
(copper wire only) three conductor power supply
cord kit rated 240 Volts (minimum) 30 Amperes
and labeled as suitable for use in a clothes dryer.
TYPICAL
THREE-WIRE
RECEPTACLE
STRAIN
RELIEF
Three Wire
Three Wire
TYPICAL
FOUR-WIRE
RECEPTACLE
STRAIN
RELIEF
Four Wire
NOTE: For more detailed information on
connecting three-wire or four-wire plugs, refer to
Section on Electrical Plug Connection.
NOTE: Four-wire cord is required for mobile
homes or where codes do not permit grounding
through neutral.
504607
POWER CORD
(Three-Wire)
STRAIN
RELIEF
NUT
D275IE0D
POWER CORD
(Four-Wire)
STRAIN
RELIEF
NUT
D006IE0A
GROUND
WIRE
"L1"
TERMINAL
GROUND
SCREW
Three-Wire Connection
GROUND
TERMINAL
WIRE
GROUND
SCREW
GROUND
WIRE
RED
WIRE
Four-Wire Connection
NOTE: Dryer is shown with access cover removed
for illustration purposes only. NEVER operate
dryer with access cover removed.
GROUND
TO NEUTRAL
WIRE
NEUTRAL
TERMINAL
"L2"
TERMINAL
CENTER
WIRE
(NEUTRAL)
STRAIN
RELIEF
(NOT SUPPLIED
WITH DRYER)
D276IE1A
"L1"
NEUTRAL
TERMINAL
"L2"
TERMINAL
BLACK
WIRE
WHITE
WIRE
(NEUTRAL)
STRAIN
RELIEF
(NOT SUPPLIED
WITH DRYER)
D171IE1A
7