Descargar Imprimir esta página

Beninca RI.6E Libro De Instrucciones página 6

Centralita a microprocesador por

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
The control unit with microcontroller for RI.6E is suitable for motors with up to 500W power.
The "Adjustment of the motor torque" can be carried out using the 5-position "POWER" switch.
This switch should be placed in the position in which, once the automation has started, it can be stopped
if it comes up against a certain amount of resistance. This acts as a safety function to protect people or
things from impact.
The "Starting function" allows the maximum motor torque to be obtained for about 1 second when the motor
is started. This starting function can be deactivated by positioning the DSW5 Dip-Switch on OFF.
Installation instructions.
a) The electrical installation and functioning logic must comply with current standards.
b) Keep the power cables (for the motor and power supply) away from the control cables (buttons, photo-
cells, radio). To avoid interference use two separate sheaths (see EN 60204-1 15.1.3).
c) Check all the connections again before supplying voltage.
d) Check that the Dip-Switch settings are as required.
e) When voltage is supplied, the "POWER" led should light up. If this is not the case, check the state of the
fuses and whether 230Vac, 50Hz power is present between terminals 1 and 2 (INPUT 230VAC - respect
phase/neutral wire position).
f) The N.C. inputs not used must be connected to the common "+V".
g) If the direction of the motor rotation is not correct, invert the "OPEN" - "CLOSE" wires of the motor as
well as the wires of the "FCA" - "FCC" limit switches.
Input/Output functions
(1,2)
INPUT 230VAC= Control unit 230Vac, 50Hz power supply (respect phase/neutral wire position).
(3,4,5)
COM/APRE/CHIUDE= Connection to the corresponding 230Vac, 50Hz motor terminals
(the earth wire (green/yellow) must be connected to the motor housing).
(6,7)
LAMP230= Connection to the 230Vac blinker.
(8,9)
OUT 24VAC= 24Vac auxiliary power supply output (1A max.).
(10,11) SCA= "Gate open warning light" contact *.
(12,13) +V= Common connection to all the control inputs.
(14)
FTC= Photocell receiver input (n.c. contact).
(15)
FCA= Limit switch input - Opening (n.c. contact).
(16)
FCC= Limit switch input - Closing (n.c. contact).
(17)
STOP= STOP button input (n.c. contact).
(18)
P.P.= STEP-by-STEP button input (n.o. contact).
(19)
APRE= OPEN button input (n.o. contact).
(20)
CHIUDE= CLOSE button input (n.o. contact).
(21,22) ANT.= Input of radio board antenna
(23,24) RX 2CH.= Radio board 2nd channel contact (n.o. contact).
(J2)
SENS_H= Input for optional anti-crash card "DA.AS"
1-2 pin: 24Vdc power supply (1 + ; 2 - )
2-3 pin: n.c. contact input
or for any other n.c. safety device (pneumatic profile, photocells, etc.)
2-3 pin: n.c. contact input;
the activation of the device connected to these terminals causes the stopping or the reversion
movement of the motor. Note: Pins 2 and 3 must be short-circuited if not in use.
* Functioning for the "Gate open warning light" contact.
• If the gate is closed, the warning light is turned off.
• If the gate is opening, the warning light flashes slow (about 1Hz).
• If the gate is closing, the warning light flashes fast (about 2Hz).
• If the gate is open or the race is interrupted manually (P.P. - STOP), the warning light remains turned on.
N.B.: The led is driven by a relay, thus the commutation can be normally heard during the normal function of
the control board.
"Select" dip-switch functions
N.B.: Every change of functions have to be done without electricity.
DSW1
This selects the type of functioning of the P.P. button and Remote control.
Off= "OPEN" - "STOP" - "CLOSE" functioning
On= "OPEN" - "CLOSE" - "OPEN" functioning.
DSW2
This enables or disables the automatic re-closing - "TCA TRIMMER".
6
Control unit with microcontroller for RI.6E

Publicidad

loading

Este manual también es adecuado para:

Ri.6kRi.6i