Descargar Imprimir esta página

Frico Thermozone AR310E/W Manual Del Usuario página 28

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 66
GB
2. Disconnect the cables to the relevant fan.
3. Remove the screws securing the fan and lift
the fan out.
4. Install the new fan as above in reverse
order.
Replacing the electric heater/coil (AR300E)
1. Mark and disconnect the cables to the
electric heater/coil.
2. Remove the mounting screws securing the
electric heater/coil in the unit and lift the
electric heater/coil out.
3. Install the new electric heater/coil in
reverse order to the above.
Replacing the water coil (AR300W)
1. Shut off the water supply to the unit.
2. Disconnect the connections to the water
coil.
3. Remove the mounting screws securing the
coil in the unit and lift the coil out.
4. Install the new coil in reverse order to the
above.
Draining the water coil (AR300W)
The drain valve is on the underside of the coil
on the connector side. It can be accessed via
the service hatch.
Trouble shooting
If the fans are not working or do not blow
properly, check the following:
•. Operating power supply to the unit;
check fuses, circuit-breaker, time switch/
thermostat (if any) that starts and stops the
unit.
•. That the air flow selector is correctly set.
•. That the position limit switch is working.
•. That the overheat protection for the motors
has not been deployed.
•. That the intake grille is not dirty.
If there is no heat, check the following:
•. That the heat demand exists; check
thermostat settings and actual temperature.
For units with electrical heating, check the
following:
•. Power supply to electric heater coil; check
fuses and circuit-breaker (if any).
•. That the overheat protection for the motors
has not been deployed.
28
AR 300 E/W
For units with water coil, check the following:
•. That the water coil is air free.
•. That there is enough water flow.
•. That incoming water is heated enough.
If the fault cannot be rectified, please contact
a qualified service technician.
Safety cut-out
(applies to units with electric heater)
If the installation is protected by means of a
safety cut-out, which trips when the electrical
appliance is connected, this may be due to
moisture in the heating element. When an
appliance containing a heater element, has
not been used for a long period and is stored
in a damp environment, moisture can enter
the element.
This should not be seen as a fault, but is
simply rectified by temporary connecting the
appliance to the mains supply via a socket
without a safety cut-out, so that the moisture
can be driven out of the element. The drying
time can vary from a few hours to a few days.
As a preventive measure the unit should
occasionally be run for a short time when it is
not being used for extended periods of time.
Safety
• Keep the areas around the air intake
and exhaust grilles free from possible
obstructions!
• During operation the surfaces of the unit
can be hot!
• The unit must not be fully or partially
covered with clothing, or similar
materials, as overheating can result in a
fire risk! (AR300E)
• This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities,
or lack of experience and knowledge,
unless they have been given supervision
or instruction concerning use of the
appliance by a person responsible for
their safety. Children should be supervised
to ensure that they do not play with the
appliance.
Technical data is on p. 10.
Controls see the following page.

Publicidad

loading

Este manual también es adecuado para:

Thermozone ar315e/wThermozone ar320e/w