VLT® Compressor Drive CDS 803
Operating Guide
3.
Press [OK] to select a parameter group.
4.
Press [▵] [▿] to browse through the parameters in the specific group.
5.
Press [OK] to select the parameter.
6.
Press [▵] [▿] to set/change the parameter value.
7.
Press [OK] to accept the change or press [Back] to go back to the previous level.

4.2.3 Data Transfer from Drive to LCP

Once the setup of a drive is complete, Danfoss recommends storing the data in the LCP or on a PC via VLT® Motion Control Tool
MCT 10.
Stop the compressor before performing this operation.
Procedure
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [1] All to LCP.
4.
Press [OK].

4.2.4 Data Transfer from LCP to Drive

Connect the LCP to another drive to copy the parameter settings to this drive as well.
Stop the compressor before performing this operation.
Procedure
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [2] All from LCP.
4.
Press [OK].

4.2.5 Restoring Factory Default Settings

There are 2 different ways of initializing the drive to factory default settings:
Via parameter 14-22 Operation Mode (this is the recommended way).
Two-finger initialization
Some parameters will not be reset, see more details in
and
1.4.2.5.2 Two-finger
Initialization.

4.2.5.1 Recommended Initialization (via Parameter 14-22 Operation Mode)

Initialization of the drive to default settings (via parameter 14-22 Operation Mode).
Procedure
1.
Select parameter 14-22 Operation Mode.
2.
Press [OK].
3.
Select [2] Initialisation and press [OK].
4.
Cut off the mains supply and wait until the display turns off.
5.
Reconnect the mains supply.
The drive is now reset, except the following parameters:
Parameter 1-06 Clockwise Direction
Parameter 1-13 Compressor Selection
Parameter 4-18 Current Limit
Parameter 8-30 Protocol
28 | Danfoss A/S © 2021.06
W A R N I N G
W A R N I N G
1.4.2.5.1 Recommended Initialization (via Parameter 14-22 Operation Mode)
Commissioning
AQ32174876762701-000301 / 130R0627