Mounting instruction
B-11260
Panic lock
4.
Locking of the passive leaf is done upwards via the tube with end plug B
9006 in the door frame as well as downwards via the solid vertical rod B
9006 e.g. in the floor socket B 9009 or B-00280.
The rod position correlates to the backset.
Installation:
For positioning, the passive-leaf control lock B 1895 requires a mounting
space with a diameter of 20 mm and a depth of 45 mm.
Cut a suitable recess in case of a flat faceplate.
Calculate lengths A1 and A2 (without
the threaded pin) of the tube with end
plug B 9006 or solid vertical rod B
9006 according to the below formula
and shorten accordingly.
L1 = Distance from centre of follower
(lever handle) up to the top corner
faceplate of the passive leaf control
lock.
L2 = Distance from centre of follower
(lever handle) up to the top corner
faceplate of the floor socket.
GB
16

Calculation of rod lengths

A1 = L1 - 113 + TL [mm]
A2 = L2 -98 [mm]
B 1895
B 9006
B-11260
B 9006
B 9016
04.2013 | 14827S | Printed in Germany