I
SECTION I: USER
I.1
AVAILABLE VERSIONS
The available versions belonging to this product range are listed below.
After having identified the unit, the following table can be used to find
out about some of the machine's features.
T
Water production unit
H
Heat pump
A
Air cooled condensation
I
Rotary DC Inverter hermetic compressors
T
High efficiency
I
Refrigerant fluid R32
n° of Compressors
1
1
1
1
1
(*) The power value used to identify the model is approximate. For the
exact value, identify the machine and consult the enclosed documents
(A1 Technical data).
Available set-ups for ELECTA-ECO_106-116 Models:
Pump:
P0 – Set up with an electronic circulator.
I.1.1
MACHINE IDENTIFICATION
The units feature a serial number plate located on the side which
includes machine identification data.
I.2
INTENDED CONDITIONS OF USE
ELECTA-ECO units are packaged cooling cycle reversible heat pumps
with air cooled evaporation/condensation and axial fans complete with
hydraulic pump.
They are suitable in air conditioning installations and industrial
processes where chilled and hot water is required, not for human
consumption.
The units are designed for outdoor installation.
DANGER!
The machine has been designed and manufactured
solely and exclusively to function as an air
evaporation heat pump; any other use is strictly
PROHIBITED. The installation of the machine in an
explosive environment is prohibited.
DANGER!
The machine is intended to be installed outdoors.
Segregate the unit if installed in areas accessible to
persons under 14 years of age.
Heating capacity (kW) (*)
6
8
10
14
16
IMPORTANT!
The unit will function correctly only if the
instructions for use are scrupulously followed, if
the specified technical spaces are complied with
during installation and if the functioning
restrictions indicated in this manual are strictly
adhered to.
I.2.1
FUNCTIONING LIMITS
In summer mode:
Maximum water inlet temperature 29°C.
In winter mode:
Minimum water inlet temperature 21°C.
Maximum water inlet temperature 55°C.
Temperature differentials permitted through the exchangers
○ Temperature differential ∆T = 4 - 8°C.
○ Minimum water pressure 0.5 Barg.
○ Maximum water pressure 2.5 Barg.
In the permitted field of operation, the compressor and inverter are
protected by a controller through continuous monitoring of the current
absorbed by the compressor, operating pressure and output
temperature. The compressor can modulate the rotation speed
automatically, regardless of the set-point request if it goes out of its
proper field of operation.
If the power cable is damaged, it must be replaced by the manufacturer,
a supporting agent or alternatively, by skilled persons so as to prevent
risks. The appliance is intended to be constantly connected to the water
supply and not connected by a hose. Should you have any questions,
contact your local dealer, an authorised service centre, agencies or
Rhoss directly.
25
ELECTA-ECO
Summer mode
Winter mode