Section 7: Control Panel/Start-Up/Testing

Control Panel Interface

DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
Before performing any maintenance on the generator, set
to OFF, remove fuses, and disconnect battery cables to
prevent accidental start up. Disconnect the cable from
the battery post indicated by a NEGATIVE, NEG or (–)
first, then remove the POSITIVE, POS or (+) cable.
When reconnecting the cables, connect the POSITIVE
cable first, the NEGATIVE cable last.

Using the AUTO/MANUAL/OFF Buttons

Button
Description of Operation
Selecting this button activates fully automatic
system operation. Automatic operation allows the
Auto
unit to automatically start and exercise the
generator according to the exercise timer settings
(see Setting the Exercise Timer section).
This button shuts down the engine and also pre-
Off
vents automatic operation and exercise of the
unit.
This button will crank and start the generator.
Manual
Transfer to standby power will not occur unless
there is a utility failure.
Figure 7-1. Generator Control Panel
Installation Guidelines For 50 Hz Air-Cooled Generators

Generator Set-Up

Upon first power up of the generator, the display interface
will begin an installation wizard. The installation wizard
will prompt the user to set the minimum settings to
operate the generator. These settings are: Current Date/
Time and Exercise Day/Time. The maintenance intervals
will be initialized when the exercise time is entered.
(000191)
The exercise settings can be changed at any time via the
"EDIT" menu.
If the 12 volt battery is disconnected or the fuse removed,
the
installation
restoration. The only difference is the display will only
prompt the customer for the current Time and Date.

Set Voltage

This 50Hz generator can be set to 220, 230, or 240VAC
during installation. Set to the appropriate voltage per the
installation.

Cold Smart Start

The Cold Smart Start feature can be enabled in the EDIT
menu. When enabled, the generator will monitor ambient
temperature and adjust its warm-up delay based on
temperature. If the ambient temperature conditions are
below 50 ºF (10 °C) upon startup in AUTO mode, the
generator will warm up for 30 seconds allowing the
engine to warm before the load is applied. If the
temperature is at or above 50 ºF (10 °C) the generator
will startup with the normal warm-up delay of 6 seconds.

Setting The Exercise Timer

This generator is equipped with a configurable exercise
timer. There are two settings for the exercise timer.
Day/Time: Once set, the generator will start and exercise
for the period defined, on the day of the week and at the
time of day specified. During this exercise period, the unit
runs for approximately 5 or 12 minutes, depending on the
model, (see
Exercise frequency (how often the exercise will take
place): It can be set to WEEKLY, BIWEEKLY or
MONTHLY. If MONTHLY is selected, the day of the
month must be selected from 1-28. The generator will
exercise on that day each month. Transfer of loads to the
generator output does not occur during the exercise
000425
cycle unless utility power is lost.
NOTE: If the installer tests the generator prior to
installation, press the "enter" button to skip setting up the
exercise timer.
Control Panel/Start-Up/Testing
wizard
will
operate
Table
7-1) and then shuts down.
upon
power
25