Proportional By External Pulses 1Xn (M); Proportional By External Pulses 1:N - Aqua HC997-1 Manual De Programación

Ocultar thumbs Ver también para HC997-1:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

HC997-999 – MOD. A
Digital multifunction solenoid metering pump
4.4.3
Proportional functioning by external pulses 1xN (M)
Every time the pump receives a pulse from the water meter it perform the desired
strokes at the programmed frequency.
If the pump receives pulses from the water meter when it's performing a dosing the
pump manages this situation in two modes: proportional or instantaneous.
Instantaneous, the pump gives instantly the remaining strokes at the set frequency and
the extra strokes at the proportional frequency spans on the time of the last two pulses
received from the water meter.
Proportional, the pump save the extra strokes and perform them at the end of the
current dosing at proportional frequency spans on the time of the last two pulses
received from the water meter.
In this functioning mode there are three parameters to set:
Example: 1xN (M) = 1x15
The pumps gives 15 strokes at 60SPM frequency every time it receives a pulse from the
water meter.
Press the
keys to set the desired values.
Press the
key to go back at the previous menu.
4.4.4
Proportional functioning by external pulses 1:N
Every time that the pump receive "N" pulses from the water meter, the pump performs a
stroke.
In this functioning mode there is only one parameter to set:
Example: 1:N = 1:15
The pump performs a stroke every 15 pulses received from the water meter.
Press the
Press the
ADSP9000026
All manuals and user guides at all-guides.com
PROPORTIONAL FUNCTIONING BY EXTERNAL PULSES
Number of strokes to perform.
Setting from 0 to250.
Frequency of the strokes per minute (SPM).
Setting from 1 to 150 or 180 (depends on the model).
Type of memory proportional or instantaneous.
Number of strokes to divide (N).
Setting from 0 to 250.
keys to set the desired values.
key to go back at the previous menu.
18/09/2015 Rev.1.5
Bat/m = 60
ENGLISH
30/100