Note On Adding Refrigerant - Airwell HDLA-025N-09M25 / YDAA-025H-09M25 Manual De Instrucciones

Ocultar thumbs Ver también para HDLA-025N-09M25 / YDAA-025H-09M25:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 182

Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 7.5m (25').
In other areas, the standard pipe length is 5m (16'). The refrigerant should be charged from the service
port on the outdoor unit's low pressure valve. The additional refrigerant to be charged can be
calculated using the following formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe
Air Purging
Additional Refrigerant
Length (m)
Method
< Standard pipe length Vacuum Pump
N/A
Liquid Side: Ø 6.35 (ø 0.25")
Liquid Side: Ø 9.52 (ø 0.375")
> Standard pipe
Vacuum Pump
R32:
R32:
length
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 24g/m
(Pipe length – standard length) x 0.13oZ/ft
(Pipe length – standard length) x 0.26oZ/ft
CAUTION
mix refrigerant types.
DO NOT
Page 33

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido