Descargar Imprimir esta página

TEC Sirius Manual Del Usuario página 49

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

PRELIMINARY
Ø
Anomaly: "minor" problems that do not bring the UPS to a halt but affect its performance or inhibit the use of some of
its functions.
CODE
A03
A04
A05
A06
A07
A08
A09
A10
A11
Input frequency outside tolerance limits
A13
Voltage on bypass line outside tolerance limits
A16
Bypass frequency outside tolerance limits
A18
Voltage on bypass line out of range
A19
A22
A25
A26
Positive branch batteries missing or battery fuses open
A27
Negative branch batteries missing or battery fuses open
A29
System temperature probe faulty
A30
A31
A32
Temperature of heat sink 1 < 0°C
A33
Temperature of heat sink 2 < 0°C
A34
Temperature of heat sink 3 < 0°C
A35
Internal battery temperature probe faulty
A36
Internal battery overtemperature
A37
External battery temperature probe faulty
A38
External battery overtemperature
A39
Positive branch batteries to be replaced
A40
Negative branch batteries to be replaced
All manuals and user guides at all-guides.com
DESCRIPTION
Inverter Desynchronized
External synchronism failed
Overvoltage on input line 1
Overvoltage on input line 2
Overvoltage on input line 3
Undervoltage on input line 1
Undervoltage on input line 2
Undervoltage on input line 3
Overcurrent peak on output
Load > user-defined threshold
Output isolator open
System temperature < 0°C
System temperature too high
97
PRELIMINARY
Ø
Fault: more critical problems than "Anomalies" in that, if they persist, they may bring the UPS to a halt.
CODE
F01
F02
Incorrect input phase direction.
F03
Input fuse 1 broken or input relay blocked (will not close)
F04
Input fuse 2 broken or input relay blocked (will not close)
F05
Input fuse 3 broken or input relay blocked (will not close)
F06
Input relay 1 blocked (always closed)
F07
Input relay 2 blocked (always closed)
F08
Input relay 3 blocked (always closed)
F09
Precharge of positive branch capacitors failed
F10
Precharge of negative branch capacitors failed
F11
F14
F17
F19
F20
F21
F22
F23
F26
F27
F28
F29
F30
F31
F32
Battery charger stage anomaly
F33
Output fuse of battery charger blown
F34
F37
Battery charger overtemperature
F42
F43
F44
DESCRIPTION
Internal communication error
BOOST stage anomaly
Sine wave of inverter distorted
Inverter stage anomaly
Positive battery overvoltage
Negative battery overvoltage
Positive battery undervoltage
Negative battery undervoltage
Overload at output
Output relay 1 blocked
Output relay 2 blocked
Output relay 3 blocked
Output fuse 1 blown
Output fuse 2 blown
Output fuse 3 blown
Heat sink overtemperature
BOOST battery 1 fuse blown
BOOST battery 2 fuse blown
BOOST battery 3 fuse blown
98

Publicidad

Solución de problemas

loading