All manuals and user guides at all-guides.com
Wire Requirements
Table 7 Wire Type Recommendation
Wire Type
Solid
Stranded
Wiring torque = 1.13 Nm (10 in-lb) rated; 1.3 Nm (12 in-lb) maximum
ATTENTION
Wiring Recommendation
When wiring without spade lugs, keep the finger-safe covers in place. Loosen the
terminal screw and route the wires through the opening in the finger-safe cover.
Tighten the terminal screw making sure the pressure plate secures the wire.
MicroLogix™ 1500 Programmable Controller Base Units
Cu-90°C (194°F)
Cu-90°C (194°F)
Be careful when stripping wires. Wire fragments that fall into
the controller could cause damage. Once wiring is complete,
be sure the base unit is free of all metal fragments before
removing protective debris strips and installing the processor
unit. Failure to remove strips before operating can cause
overheating.
Wire Size (2 wire maximum per terminal
screw)
#14 to #22 AWG
#14 to #22 AWG
Finger-Safe Cover
Publication 1764-IN001A-ML-P
13