Descargar Imprimir esta página

Allen-Bradley MicroLogix 1500 Instrucciones De Instalación página 20

Ocultar thumbs Ver también para MicroLogix 1500:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 81
All manuals and user guides at all-guides.com
20
MicroLogix™ 1500 Programmable Controller Base Units
Table 13 Working Voltage
Specification
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
FET Output Group to Backplane Isolation
and FET Outputs Group to Group
Relay Output Group to Backplane
Isolation
Relay Output Group to Relay and FET
Output Group Isolation
Publication 1764-IN001A-ML-P
1764-28BXB
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)

Hide quick links:

Publicidad

loading

Este manual también es adecuado para:

1764-24awa1764-24bwa1764-28bxb