Table 13 Working Voltage
Specification
Power Supply Input to Backplane
Isolation
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Output Group to Backplane Isolation
Output Group to Output Group Isolation
Specification
Power Supply Input to Backplane
Isolation
Power Supply User 24V Output to
Backplane Isolation
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Output Group to Backplane Isolation
Output Group to Output Group Isolation. Verified by one of the following dielectric tests: 1836V
MicroLogix™ 1500 Programmable Controller Base Units
1764-L24AWA
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 151V
ac for 1 second or 2145V dc for 1 second
132V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation).
1764-24BWA
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 600V
ac for 1 second or 848V dc for 1 second
50V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation).
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)
Publication 1764-IN001A-ML-P
19

Hide quick links:

Publicidad

loading

Este manual también es adecuado para:

1764-24awa1764-24bwa1764-28bxb