Cool only and heat pump multisplit units Installation Instructions ..........................12 - 16 Johnson Controls Manufacturing España, S.L. participa en el Programa de Certificación EUROVENT. Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification Programme. Los productos se corresponden con los relacionados en el Directorio EUROVENT de Productos Products are as listed in the EUROVENT Directory of Certified Products, in the program AC1, AC2, Certificados, en el programa AC1, AC2, AC3, LCP y FC.
Página 5
Fig.18 Fig.19 Fig.20 Panel frontal Pantalla luminosa Cable de interconexión Front panel Display Interconnecting cable Painel frontal Ecrã Cabo de interligação Filtros Calefacción Conexiones frigoríficas (ver dibujo Filters Heat adjunto unidad exterior) Filtros Aquecimento Cooling connections (see outdoor...
Página 6
Manómetro Tubo de gás Salida de desagüe Pressure gauge Gas pipe Drain outlet Manómetro Tubo de gás Saída de desaguamento Tuerca Bomba de vacío Vacuum pump Porca Bomba de vácuo Tubo de líquido Soporte metálico Liquid pipe Metal support Tubo de líquido...
Instrucciones de instalación Precaución - Sitios expuestos a gases sulfúricos. Este aparato debe ser instalado y utilizado - Lugares donde se generen ondas de alta Inspección conforme a: frecuencia, producidas por equipos de En su recepción, inspeccionar la mercan- - Reglamento Electrotécnico de...
Espacios libres, unidad exterior talados en al unidad exterior, tanto el tubo - El refrigerante R-410A debe ser cargado de mayor diámetro como el de menor, es- siempre en forma líquida. Si la botella no Se requiere un espacio libre mínimo alre- tán en el lado de baja presión relativa del...
Presión de trabajo 5,1 como el que se muestra en la figura 20. La Atención Mpa, presión de ruptura 27,4 Mpa. Rosca instalación de este sistema consiste en la - Todo el conexionado eléctrico ½”...
Installation Instructions Installing the indoor unit - Low Voltage Electrotechnical Regulations. Inspection Attach the mounting plate to the wall. Tighten - Safety Regulations for Cooling screws lightly. Upon reception, inspect the equipment and Plants and Installations. Level the mounting plate and then finish notify both the carrier and the insurance - Regulations on Pressure Equipment.
Página 14
Installation of interconnecting Process 15 minutes. Should this not be possible, a flow of dry nitrogen should be established. pipes - Fit an adapter to the pump to avoid - POE oil cannot be mixed with mineral oil.
Routine check after 7. For heat pump models, fasten operating cable with the corresponding flange. Tubing diameter Minimum thickness installation mm (inches Operational test Outdoor unit 1. Prior to test: 1. Remove side cover. - Do not connect unit until completely 6,35 (1/4")
Electrical connections Fig.22 EMHC 18, 21, 24 POWER SUPPLY 230V/1ph/50Hz MA AZ AM/V OUTDOOR N(1) 2 N(1) 2 UNIT AM/V N MA VT NJ AM/V INDOOR UNITS N(1) 2 N(1) 2 AM/V: Yellow/ Green AZ: Blue MA: Brown...
Página 17
Especificaciones técnicas Indoor units (9000 Btu/h) 2 x EMKC-09 1 x EMKC-09 Indoor units (12000 Btu/h) 1 x EMKC-12 2 x EMKC-12 Outdoor unit EMJC-18 EMJC-21 EMJC-24 Cooling capacity Heating capacity Power supply V.ph.Hz 230.1.50 Indoor wall units...
Página 19
DECLARACION CE DE CONFORMIDAD SOBRE MAQUINAS JOHNSON CONTROLS MANUFACTURING ESPAÑA, S.L. FABRICANTE: DIRECCIÓN: Paseo Espronceda, 278, 08204 SABADELL Certificamos que el equipo descrito, ha sido diseñado, fabricado y probado de conformidad con los requisitos básicos de la Directiva de Equipos a presión 97/23/CEE y sus correspondientes módulos de aplicación.