Gree GMV-ND22PL/B-T Manual Del Propietário página 13

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit
( 1 ) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig 4.3.2.
( 2 ) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm.
①metal clamp(accessory)
②drain hose(accessory)
( 3 ) Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig.4.3.3.
①metal clamp(accessory)
②thermal sponge(accessory)
( 4 ) When connecting several drain pipes, follow the instruction as indicated in Fig 4.3.4. Choose the
drain collecting pipe that matches with unit capacity.
5
(5)For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
6
For indoor units that have high pressure at the outlet of drain pipe, use water-sealed joint.
7
Install the water-sealed joint according to Fig.4.3.5.
8
Each unit should be installed with one water-sealed joint.
9
The horizontal pipe can be connected to vertical pipe in the same level; please select the
connection way as shown in following fig.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Fig 4.3.2
Fig 4.3.5
Fig 4.3.3
Fig 4.3.4
10

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido