6 Commissioning
Result
44
TT grid: damage caused by missing external fault-current
circuit breaker.
If the device is operated in a TT grid, an external fault-current
circuit breaker is required.
| For TT grids, install an additional external fault-current
circuit breaker.
GRID TYPE
TN
14.Press the button and hold it for longer to confirm the entry.
COUNTRY
ITALY
The line flashes
15.Press the button repeatedly until the required country
appears.
Selecting the language sets a country-specific set of
parameters. The manufacturer has defined country-specific
parameter sets in line with country-specific standards. You
only have a period of 5 minutes after commissioning in which
to select a different country with its corresponding parameter
set. To do this, use the button to navigate to the SERVICE
menu. This setting can then be changed only via
StringInverter setup.
The inverter functions only if a set of parameters is set.
If you want to use the device in a country that is not listed in
the display, Contact the manufacturer's service centre
(contact information on the back of the manual).
COUNTRY
GERMANY
16.Press the button and hold it for longer to confirm the entry.
The inverter is commissioned.
If the inverter does not supply current, check the installation.
Make sure that
| Wires are correctly connected to the mains power supply.
| All cables are connected tightly.