3 609 929 B61/2008-09 | SE352/SE352M
1. Switch off the power supply to the
BT356 card rack or SB35x system box
and allow for a discharging time of
10 seconds.
2. Insert the SE352/SE352M control unit in
the respective slot in the BT356 card
rack or SB35x system box.
3. Tighten the knurled bolts on the front.
Make sure that the front panel is flush to
the BT356 card rack or SB35x system
box by tightening the knurled bolts.
7
Commissioning
CAUTION
Risk of damage to persons
and property!
Commissioning of the SE352/
SE352M control unit requires ba-
sic mechanical and electrical
knowledge.
y
Only qualified personnel (see
"Personnel qualifications" on
page 18) are authorized to
commission the system.
y
Once the device has been
switched off, it cannot be
switched back on again until at
least 30 seconds have
elapsed.
Bosch Rexroth AG
i
NOTE!
If you use the components in an existing
system as a replacement or an extension,
you must install the firmware that is used in
the system.
The firmware versions and service packs
created up to the time of delivery can be
found on the system stick. If newer firm-
ware versions and service packs have
been created before commissioning, they
can be downloaded from the Rexroth
homepage.
Before commissioning, check that the plug
connections are firmly fitted. Proceed as
follows for commissioning:
1. Check whether the battery is correctly
seated in the battery holder. If not, insert
a battery according to the instructions in
Section "9 Maintenance and repair" on
page 26.
2. Insert the SE352/SE352M control unit in
the card rack or system box.
3. If necessary, insert IMxxx interface
modules in the SE352/SE352M control
unit.
4. Close off slots that are not occupied with
interface modules using dummy panels.
5. Turn on the voltage supply for the card
rack or system box.
6. Connect the operating computer and set
the time with the BS350.
7. Configure the interfaces and program the
tightening system.