BTL7-C/E5 _ _ -M _ _ _ _ -P-S32/KA _ _
Micropulse Transducer in a Profile Housing

Electrical connection

Pin
Cable color BTL7-C508-...
BTL7-E508-...
1
YE yellow
2
GY gray
0...10 V
3
PK pink
4
RD red
5
GN green
6
BU blue
7
BN brown
8
WH white
Installing the transducer (continued)
The transducer is electrically isolated from the machine
with the supplied insulating bushes.
1. Guide the transducer into the mounting clamps.
2. Attach transducer to the base using mounting screws
(tighten screws in the clamps with max. 2 Nm).
3. Insert magnet (accessories).
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the transducer and controller using a shielded
cable.
Shielding: Copper filament braided, at least 85%
coverage.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the transducer side, the cable
shielding is connected to the housing. Ground the
cable shielding on the controller side (connect with the
protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive system.
It is important to maintain adequate distance between the
transducer and strong, external magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible). The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-C/E
Max. 100 m 1)
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
www.balluff.com
BTL7-C509-...
BTL7-C512-...
BTL7-E509-...
BTL7-E512-...
-C: 0...20 mA 1)
-E: 4...20 mA 1)
0 V
10...0 V
La (communication line)
Not used 2)
GND 3)
10...30 V
Lb (communication line)
BTL7-C513-...
BTL7-E513-...
-C: 20...0 mA 1)
-E: 20...4 mA 1)
0...10 V
10...0 V
Noise elimination
To avoid equipotential bonding - a current flow - through
the cable shield, please note the following:
Use insulating bushes
Put the control cabinet and the system in which the
transducer is located to the same ground potential.
Startup
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
regularly (especially after replacing the transducer or
after repair by the manufacturer). Recalibrate the
transducer, if necessary.
The calibration procedure is described in the
comprehensive user's guide.
Operating notes
Check the function of the transducer and all associated
components on a regular basis.
Take the position measuring system out of operation
whenever there is a malfunction.
Secure the system against unauthorized use.
Pin assignment of S32 connector
(view of connector pins of
transducer)
1) Factory setting, can be freely
configured with the PC software.
2) Unassigned leads can be connected
to GND on the controller side but not
to the shield.
3) Reference potential for supply voltage
and EMC-GND.