Quarterly Maintenance; Cleaning And Fi Lter Maintenance; Putting Out Of Service And Recycling - S&P COR-PRO 1000 W 15 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

12.1. QUARTERLY MAINTENANCE

• Check the integrity of suspension or anchoring elements together with tightening of connection elements.
Check the tightness of screws on front discharge diffusers.
• Check internal inlet "plenum" space and remove any residue or object present.
• Check if motor scroll and impeller are clean. Do not wash the motor with water and in any case wipe it with
water and if necessary wipe it with a damp cloth to avoid damaging the motor winding. Do not start up the
air curtain during next 60 minutes after cleaning to allow moisture to disappear. In case of cleaning blades,
do not apply excessive strength as they could be damaged.
• Check the safety of the unit regarding risks of electric shock in accordance with local applicable regulations
together with grounding verifi cation.
• Check the tightness of the water coil together with the connection joints. If there is a fi lter in the water sys-
tem before the air curtain, clean it and then check the operation of the coil.
12.2. CLEANING AND FILTER MAINTENANCE
COR-PRO W models incorporate air fi lters in the inlet side. This should be cleaned regularly to ensure the
effi ciency and performance of the air curtain. Cleanliness depends on the local conditions where the curtain is
installed; it is recommended to check the fi lter and clean it once a month. A clogged fi lter does not represent
a safety risk, but curtain performance may change and motor may suffer.
Filter removal:
• Remove plastic protectors to access the fastening screws of
the inspection door located on the lower face of the air cur-
tain.
• Loosen the fastening screws using an Allen key and tilt the
inspection door.
• Through the inspection door, release the fi lter by rotating the
retaining locks located on the sides of the fi lter.
• Remove the fi lter and clean dust particles. Replace the fi lter
(accessory under description AFR COR-PRO W) if the bloc-
kage is evident even after cleaning of if fi lter material shows
damage.
Only use original fi lters. Other air fi lters may have a quite different fi ltration class or pressure drop. This could
provoke performance reduction or motor overheating causing failure hazard.

13. PUTTING OUT OF SERVICE AND RECYCLING

EEC legislation and our consideration of future generations mean that we should always recycle materials
where possible; please do not forget to deposit all packaging in the appropriate recycling bins. If your device
is also labeled with this symbol, please take it to the nearest Waste Management Plant at the end of its servi-
ceable life.
Retaining
locks
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cor-pro 1500 w 24Cor-pro 2000 w 36Cor-pro 2500 w 45

Tabla de contenido