The generating set GE 40 is a unit which transforms the mechanical energy, generated by endothermic engine, into electric
energy, through an alternator.
Is meant for industrial and professional use, powered by an endothermic engine; it is composed of various main parts such as:
engine, alternator, electric and electronic controls, the fairing or a protective structure.
The assembling is made on a steel structure, on which are provided elastic support which must damp the vibrations and also
eliminate sounds which would produce noise.
Technical data
GENERATOR
Three-phase generation (*stand-by)
Three-phase generation (**P.R.P.)
Single-phase generation
Frequency
Power factor (cos ϕ ϕ ϕ ϕ ϕ )
ALTERNATOR
Type
Insulating class
ENGINE
Mark
Model
Type
Displacement
Cylinders
Output
Speed
Fuel consumption
Cooling system
Engine oil capacity
Starter
Fuel
GENERAL SPECIFICATIONS
Battery
Tank capacity
Running time (al 75%)
Protection
Dimensions max. su base Lxlxh *
Weight *
Noise level
* Dimensions and weight are inclusive of all parts without optional CTM
Declared powers at the following ambient conditions: temperature 20*C, relative humidity 30% altitude 100 m above sea level.
In an approximative way one reduces: of 1% every 100 m altitude and of 2.5% for every 5°C above 25°C.
For possible modifications or changes to be brought on the engines, with climate conditions different from those above
mentioned, please call our Assistance Authorized Centers.
The machine respects the noise limits, expressed in sound power, given in the a.m. directives.
These limits can be used to judge the sound level produced on site.
For example: the sound power level of 100 LWA.
The sound pressure (noise produced) at 7 meters distance is about 75dBA (the limit value less 25).
To calculate the sound level at other distances use this formula:
ry²
dBA x = dBA y + 10 log
rx²
At 4 meters the noise level becomes:
75 dBA + 10 log
= 80 dBA
Technical data
GE 40 VS
910 Kg
95 LWA (70 dB(A) - 7 m)
ACOUSTIC POWER LEVEL
44 kVA (35.2 kW)/ 400 V / 63.5 A
40 kVA (32 kW)/ 400 V / 57.8 A
14.6 kVA / 230 V / 63.5 A
50 Hz
0.8
self-excited, self-regulated, brushless
three-phase, synchronous
H
VM SUN
3105 T
4-Temps
2985 cm
3
3 - Stroke
31 kW (42 HP)
1500 rpm
225 g/kWh
Air
6.9 l
Electric
Gasoline
12V - 100 Ah
68 l
9 h
IP 23
1940x850x1080
OUTPUT
GE 40 VS - VSX
GE 40 VSX
930 Kg
92 LWA (67 dB(A) - 7 m)
M
51

Publicidad