CONNECTIONS
STANDBY
The Standby function can stop the pump remotely. When a dry contact or open collector
signal is received to the Standby inputs, the pump ceases operation as long as the signal
is present. In standby, the POWER/STANDBY LED is lit solid red.
Dry Contact Relay Output
Open Collector Output
For connection to a dry contact
– There is no polarity to observe.
– Connect relay to Standby (-), position 19 and Standby (+), position 20.
For connection to an Open Collector output
– Polarity must be observed.
– Connect OC positive to Standby (+), position 20.
– Connect OC common to Standby (-), position 19.
1
2
NC
NC
NC
NC
11
12
13
16
S Fixed & Variable Series
continued
Controller
Controller
3
4
5
6
Transfer
Transfer
NC
Relay
Relay
(b)
(a)
NC
NC
NC
14
15
16
www.stenner.com
Pump
Input
7
8
9
Run
Leak
Leak
Run
Detect
Relay
Relay
Detect
Relay (b)
(b)
(a)
Relay (a)
Standby
Standby
NC
NC
(
)
17
18
19
Pump
Input
10
+
(
)
20