Cabling
Heavy duty fusible safety switches
Cabling / Fusible safety switches
Cable entry/exit locations: Top entry-bottom exit.
Cable entry/exit through top/bottom endwalls maximize the
cable bending area. All cable entry/exit must be in accordance
with the National Electrical Code and all other local codes.
See the chapter Wiring. In 200 A switches use Hex key / wrench
size 3/8 and in 400 A / 600 A switches use Hex key / wrench
size 1/2.
Heavy duty fusible safety switch
AMPS
Line side (switch terminals) terminal lugs
Terminal lug
Torque: wire tightening for Cu and Al cables
Lug mounting torque
Wire range
Load side (fuse base terminals) terminal lugs
Terminal lug
Torque: wire tightening for Cu and Al cables
Lug mounting torque
Wire range
Ground bus (2 lugs)
Screwdriver, tool
Ground bus catalog number
Torque: wire tightening for Cu and Al cables
Maximum stud mounting torque
Wire range
EOH364K
A
200
OZXA-400
lbs.in
375
Nm
41.8
lbs.in
228
Nm
25.4
kcmil
#2 - 600
mm
2
35 - 300
OZXA-400
lbs.in
375
Nm
41.8
lbs.in
228
Nm
25.4
kcmil
#2 - 600
mm
2
35 - 300
Slot
OZXG1
lbs.in
50
Nm
5.6
lbs.in
72
Nm
8.1
AWG, kcmil
#14 - 2
2
mm
2.5 - 35
Instruction Bulletin EOH364K, EOH365K, EOH366K, 1SCC340031M1401 / A | Cabling 1/7
WARNING
To avoid hazard of electric shock, turn off and lock out all power
sources before installing or performing maintenance on this equipment.
EOH365K
400
OZXA-800E
500
55.7
480
53.5
(2) #2 - 600
2 × 35 - 300
OZXA-800
500
55.7
480
53.5
#3 - 900 or 2 × 350
25 - 400 or 2 × 185
5/16" Hex
OZXG2
275
31.1
72
8.1
#6 - 250 kcmil
10 - 120
1
EOH366K
600
OZXA-800
500
55.7
480
53.5
(2) #2 - 600
2 × 35 - 300
OZXA-800
500
55.7
480
53.5
(2) #2 - 600
2 × 35 - 300
5/16" Hex
OZXG2
275
31.1
72
8.1
#6 - 250 kcmil
10 - 120