Block Diagram; Trimpots Function; Trimpots Adjustment - WEG GRT7-TH4 Manual De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6 BLOCK DIAGRAM

Reference value
Analog input
± 9 Vdc(1)

7 TRIMPOTS FUNCTION

P1: Voltage adjustment
P2: Droop adjustment².
P3: Stability - 2 adjustment.
P4: Stability - 1 adjustment.
P5: Under frequency adjustment.

8 TRIMPOTS ADJUSTMENT

P1: Rotating CW, voltage increases.
P2: Rotating CW, reactive compensation range increases.
P3: Rotating CW, dynamic response will be slower.
P4: Rotating CW, dynamic response will be slower.
P5: Rotating CW, U/F range increases and rotating CCW, it decreases.
NOTE
1. A potentiometer may be connected for fine voltage adjustment (5 k / 3 W) at terminals 6 and 7.
¹ Only for models TH4 E and TH4 PE.
2
Available only for models TH4.
PID
+
- +
+
U/F
Sensing
DROOP ²
Automatic
field flashing
Power stage
Automatic Voltage Regulator - GRT7-TH4 | 13
www.weg.net
Excitation field
G

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Grt7-th4 pGrt7-th4 eGrt7-th4 peGrt7-th5

Tabla de contenido