Enter a 4-digit time using the 24-hour clock format (HH:MM) to set the test transmission time of day. Valid entries are from 00 to 23
for the hours (HH) and 00 to 59 for the minutes (MM). To disable the test transmission time of day enter 9999 in this section.
NOTE: The internal date and time will automatically be programmed when it communicates with the primary receiver.
[125] Ethernet Test Transmission Cycle
Default (000000)
This value represents the interval in between test transmissions in minutes. This section can be programmed with
000000 to 999999 minutes. Once the unit has sent the initial periodic test transmission, all future test transmissions will be offset by
the programmed number of minutes.
NOTE: The minimum programmable valid interval is 5 minutes, programming an interval of less then 5 minutes will disable the test
transmission.

GPRS Receiver 1 Options

[201] GPRS Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting
heartbeat signals to the central station receiver. Signals received from the control panel will use the control panel account number.
Valid entries will range from 0000000001 to FFFFFFFFFE hexadecimal.
[202] GPRS Receiver 1 DNIS
Default (000000)
The DNIS is used in addition to the Account Code to to identify the Communicator module as the central station. Valid entries range
from 000000 to 0FFFFF hexadecimal.
[203] GPRS Receiver 1 IP Address
Default (0.0.0.0)
Enter the GPRS receiver 1 IP address. This information will be provided by your central station. Note that when a valid address has
been entered, the GPRS will be considered to be enabled and will communicate events over the GPRS channel. The address must be
entered as four 3-digit entries (e.g. 192.168.1.101). Each 3-digit segment of the address must be within a valid range of 000 to 255.
[204] GPRS Receiver 1 Remote Port
Default (3061)
This option determines the port of GPRS receiver 1. You can set the value of this port in case your installation is located behind a fire-
wall, and must be assigned a particular port number as determined by your central station system administrator. Valid entries range
from 0000 to FFFF hexadecimal.
[205] GPRS Receiver 1 APN
Default ( )
The APN (Access Point Name) identifies the GPRS network the communicator will connect to. This information is available from your
network carrier.
NOTE: This option is not accessible via PC1616/PC1832/PC1864 keypad programming.

GPRS Receiver 2 Options

[211] GPRS Receiver 2 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting sig-
nals to the central station receiver. Signals received on the control panel will use the control panel account number. Valid entries will
range from 0000000001 to FFFFFFFFFE hexadecimal.
[212] GPRS Receiver 2 DNIS
Default (000000)
The DNIS is used in addition to the Account Code to to identify the Communicator module as the central station. Valid entries range
from 000000 to 0FFFFF hexadecimal.
[213] GPRS Receiver 2 IP Address
Default (0.0.0.0)
Enter the GPRS receiver 2 IP address. This information will be provided by your central station. Note that when a valid address has
been entered, the GPRS will be considered to be enabled and will communicate events over the GPRS channel. The address must be
entered as four 3-digit entries (e.g. 192.168.1.101). Each 3-digit segment of the address must be within a valid range of 000 to 255.
[214] GPRS Receiver 2 Remote Port
Default (3061)
This option determines the port of GPRS receiver 2. You can set the value of this port in case your installation is located behind a fire-
wall, and must be assigned a particular port number as determined by your central station system administrator. Valid entries range
from 0000 to FFFF hexadecimal.
NOTE: Do not program GPRS Receiver 1 and GPRS Receiver 2 to communicate to the same receiver.
[215] GPRS Receiver 2 APN
Default ( )
The APN (Access Point Name) identifies the GPRS network the communicator will connect to. This information is available from your
network carrier.
NOTE: This option is not accessible via PC1616/PC1832/PC1864 keypad programming.

GPRS Options

[221] GPRS Public APN
Default ( )
When your communicator is operating on a private APN, you can use this option to switch to a public APN for DLS sessions. This
information is available from your network carrier.
The APN (Access Point Name) identifies the GPRS network the communicator will connect to.
NOTE: This option is not accessible via PC1616/PC1832/PC1864 keypad programming.
[222] GPRS Login User Name
Default ( )
TEST TRANSMISSION INTERVAL
Daily
Weekly
Monthly
Table 6: Ethernet Test Transmission Interval
PROGRAMMED MINUTES
001440
010080
043200
12