7.2
Parameter settings via the service code
The parameters of the boiler controller have been configured in the factory in accordance with the following table.
These parameters can only be changed with the service code. Take the following actions to activate the program memory:
1.
Press the
and the
button simultaneously, until a
2.
Use the
button to enter
3.
Use the
button to set the parameter you wish to configure, on the service display.
4.
Use the and button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the
The boiler controller has now been reprogrammed.
Note
Pressing the
button will take you out of the menu without saving the parameter changes.
Example: Change maximum CH power
1.
Press the
and the
button simultaneously.
15
2.
Use the button to go to
3.
Press the
button 3 x. 60 and 3 will appear on the display.
4.
Use the button to change the 60 to 70.
P
5.
Press the
button until
6.
The change has now been implemented. The maximum CH power has been increased from 60 to 70 %.
Parameter
Description
0
Service code [15]
1
Installation type
2
CH pump setting
3
Set maximum CH power
3.
Maximum capacity modulating CH pump
4
Set maximum hot water power
5
Min. leaving water temperature of the fuel
line
5.
Max setting value leaving water
temperature via operating panel
6
Min. outdoor temperature of the fuel line
7
Max. outdoor temperature of the fuel line
8
CH pump post-running time after CH
operation
9
CH pump post-running time after boiler
operation
A
Setting three-way valve or electrical valve
0
appears on the service display and a
15
(service code) on the temperature display.
.
appears.
RKOMBG*AAV1
22
-
0
0
60
80
99
25
90
-7
25
1
1
0
P
button until
appears on the service display.
28
33
Settings reach
-
-
Access to installers settings, the service code must be
entered (=15)
0
0
0= combi
1= Solo RKOMBG22AAV1 + boiler
2= Tap (hot water only)
3= Solo
0
0
0= pump post-running time active
1= pump continuously active
2 – 5 = Not active
60
60
Setting reach set value parameter c up to 100%
(100 % = 99 + 1x )
80
80
Setting reach set value parameter c. up to 100%
99
99
Setting reach set value parameter d up to 100%
25
25
Setting reach 10°C to set value parameter 5
90
90
Setting reach 30°C to 90°C
-7
-7
Setting reach -30 to 10°C
25
25
Setting reach 15°C to 30°C
1
1
Setting reach 0 to 15 minutes
1
1
Setting reach 0 to 15 minutes (n/a to Combi unit)
0
0
0= powered during CH operation
1= powered during hot water operation and rest
2= powered during every heat request (CH, hot water and
continuous heating function)
3= group regulation
4 and higher = Not applicable
0
on the temperature display.
40