Battery Replacement Door
2) remove the battery door located on the front panel; 3) pull batteries
partially out of the case; 4) make a detailed sketch of the batteries and
the polarity, color and connection of all cables; 5) disconnect battery
terminals; 6) dispose of used batteries; 7) reconnect replacement
batteries exactly as original batteries were; 8) push batteries back into
case and replace cover.*
* You may not receive full runtime until your replacement batteries have fully charged.
Storage & Service
Storage
Turn your UPS OFF: first, engage the ON/Standby Switch and release it to place your
UPS in the "Standby" mode; then set the System Enable Switch* to "DISABLE"; finally,
disconnect the UPS power cord from the wall outlet. If you plan on storing your UPS
for an extended period of time, recharge the UPS batteries once every three months.
Follow steps #1 and #3 in the Installation section and allow the UPS to charge from
4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time,
they will suffer permanent loss of capacity.
* The location of the switch varies by model. See page 3.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the
ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing
the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose
a copy of your sales receipt.
Specifications
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
Battery Recharge Time:
Suggested Circuit:
Approvals:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
Battery Recharge Time:
Suggested Circuit:
Approvals:
Output Capacity (VA/Watts):
Battery Runtime (Half Load/Full Load) Min.:
Battery Recharge Time:
Suggested Circuit:
Approvals:
ALL MODELS:
Input Voltage/Frequency (120V/60 Hz); On Line Input Voltage Range (87 - 140 Volts); Voltage-Regulated Output Voltage Range
(120V +/- 9%); On Battery Output Voltage Range (120V +/- 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery
Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection
Modes (H to N, H to G, N to G).
Under normal conditions, the original batteries in your UPS will
last several years. Battery replacement should only be performed
by qualified service personnel. Refer to "Battery Warnings" in the
Safety section on page 2. When replacing batteries, qualified
service personnel should follow this procedure: 1) turn UPS OFF;
SMART 700 RM
700/450
28/12
2-4 hrs.
15 amp
UL, cUL
SMART 1400 RM
1400/940
26/10
2-4 hrs.
15 amp
UL, cUL
SMART 2200 RM XL
2200/1750
29+/13+
2-4 hrs.
20-amp dedicated
UL, cUL
SMART 1050 RM
1050/705
23/8
2-4 hrs.
15 amp
UL, cUL
SMART 2200 RM
2200/1750
29/13
2-4 hrs.
15- or 20- amp dedicated
UL, cUL
SMART 3000 RM
3000/2400
23+/7+
2-4 hrs.
30-amp dedicated
UL, cUL
7