Technical Data; Dimensions; Field Of Operation - Riello PRESS 60 N/ECO Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.

TECHNICAL DATA

2.1
TECHNICAL DATA
TYPE
Thermal power - Capacity
Fuel
Electrical supply
Motor
230V - 400V
Ignition transformer
Heaters
Electrical intake power
Pump
2.2

DIMENSIONS

Boiler plate
D2686
NOTE
The weight of the rear part of the pumping assembly exerts flexure stress on the guides; you are advised
to hold the burner while it is being extracted so as not damage the flame disc and the said guides.
For long - head version.
*
Use the pin extensions provided to move the burner back.
2.3
FIELD OF OPERATION (2 nozzles in operation)
When the burner operates with only one nozzle, the pressurization conditions are better and no problems
arise. Minimal fuel capacity with one only nozzle: 15 kg/h - 171 kW.
6202
628 T80
171/342 - 684 kW
Oil with max. viscosity at 50° C 115 sq.mm/s (15° E)
±
Three-phase, 230 V
±
400 V
Fan:
3.4A - 2A
Pump:
2.5A - 1.4A
Primary 2 A
Secondary 2 x 6.5 kV – 35 mA
4.2 kW
5.9 kW
100 kg/h at 20 bar
834
400
79
GB
2
15/30 - 60 kg/h
~
10%
60Hz without neutral
~
10%
60Hz with neutral
Burner
245
*
D2723
Thermal power
625
290
D2715
kg/h
kW