2.5
Terminal box
2.5
Terminal box
Wiring with "d" terminal box
• Terminal box is arranged according to the
feet (for IM1... or IM2... mounting).
The terminal box axis is normally perpen-
dicular to the laying surface.
Optionally, it can be supplied for "right" or
"left" mount according to a front view of
the motor, main shaft end side (without
surcharge).
Note: the terminal box position can only
be changed at the factory.
• Cable output position
In standard executions, the cable output is
on the right (looking at the motor from the
shaft side).
All other options must be requested at the
time of the order using the same reference
(upper, lower, left, right, front and rear
cable output).
• "d" cable gland
In "EEx-d" motors, the cable gland aids
the flameproof enclosure closing.
The user MUST choose a cable with a
diameter on the sealing membrane side
corresponding to the cable gland specifi-
cation, as well as use a device for hooking
the cable on the cable external diameter
side.
In standard conditions, motors are sup-
plied with an EEx-d cable gland with cable
hook.
On the sealing membrane side, the cable
must have a diameter of 11 ± 0.5 mm
(Figure 2 C).
In standard conditions, 2-speed motors
have two cable glands.
Options for cable gland "d"
- terminal box supplied without cable gland,
with threaded hole ISO M
- gasket Ø 9 or 13 mm for cable gland
- additional cable gland (standard model) or
additional hole
- cable gland with shielding extension
- cable gland for armoured cable or special
cable gland.
Standard
Left
(option)
Fig. 2 B
Cable gland
Fig. 2 C
Options for terminal box "e"
• Increased safety EEx-e terminal box:
- available for ventilated three-phase
motors with 63 to 80 HA
- IP55 (IP65 optional); maximum voltage
690V, waterproof connection system,
removable between terminal box and
frame supplied with an EEx-e cable gland
for a non-armoured cable with 7.5 to
13 mm diameter (M20 ISO). Cable gland
option: contact us for further information.
Other options
• Motors without terminal board.
• Motor with cable output:
- available for the three-phase series
- power supply cable (4 or 7 wires)
connected at the factory
- small overall dimensions, thanks to the
elimination of the terminal box on the
ventilated three-phase motors
- dimensions and further features: contact
us for further information.
• Manual control on/off switch built in the
terminal box (only HA 63-71-80).
Right
(option)
Gasket
Standard
aluminium cable
gland for frame size
56 to 80,
(sides in max mm)
GB
Cable hooking
Sealing
membrane
Outer
diameter
17