Rated frequency
Power factor cos phi
Grid connection
Maximum output power
Rated power
Nominal output current / phase
Total harmonic distortion
AC overvoltage category
5)
Current (inrush)
Maximum output fault current / duration
General data
Night-time power loss = standby consumption
European efficiency (580 / 800 / 930 V
Maximum efficiency
Safety class
EMC emission class
Pollution degree
Permitted ambient temperature
with built-in "AC disconnector" option
Permitted storage temperature
Relative humidity
Sound pressure level (580 V
Protection class
Dimensions (height x width x depth)
Weight
Inverter Topology
Protection devices
DC disconnector
Cooling principle
RCMU
DC isolation measurement
Overload performance
Active anti-islanding method
WLAN
Frequency range
)
DC
)
DC
50 / 60 Hz
0 - 1 ind./cap.
3~ NPE 380 / 220 V
3~ NPE 400 / 230 V
50 kW
50 kW
75.8 A / 72.5 A
< 3%
209 A peak /
30.5 A rms over 2.1 ms
37.2 A / 19.4 ms
15 W
98.2 / 97.7 / 97.3%
98.5%
- 40 °C - +65 °C
-30 °C - +65 °C
- 40 °C - +70 °C
0 - 100%
68.5 dB(A) (ref. 20 µPA)
IP65
755 x 1109 x 346 mm
80 kg
Non-isolated transformer-
less
Integrated
Controlled forced-air ven-
tilation
Integrated
Integrated
Operating point shift
power limitation
Frequency shift method
2412 - 2462 MHz
1)
2)
AC
AC
3
4)
1
B
3
2)
95