Output frequency selection
Frequency
50 Hz
60 Hz
To save energy from the battery in no load operation, DIP switch 4 can be used to enable the Power
Saving Mode.
Power Saving Mode
Mode
Power Saving OFF
Power Saving ON
The Power Saving Mode scans the output and compares the detected load to the set threshold
values. When a load is detected which is lower than the Power Save threshold value, the inverter
switches into Power Saving Mode. When a load is detected which is higher than the Wake Up
threshold value, the inverter is switched on.
The threshold values for Power Save and Wake Up are both set with the variable resistor. The
variable resistor is located on the right of the DIP switches. The minimum and maximum threshold
values are described in the following table.
Power saving load adjustment
Threshold type
Power save threshold
Wake up threshold
DIP switch 3
OFF
ON
DIP switch 4
OFF
ON
Min
Max
20 VA
110 VA
40 VA
160 VA
15
ENGLISH