Voltage between the positive and negative terminals of the electronics
Term
U
Cut-in voltage of the electronics
ON
U
Cut-off voltage of the electronics
OFF
Compressor is not running (connected to AC supply)
Problem
No voltage
Voltage is present but
the compressor doesn't
run
Electric circuit between
the pins in the compres-
sor interrupted
Poor cooling, increase in interior temperature
Problem
Compressor runs for a
long time/continuously
Compressor does not
run often
EN
Possible cause
Connection supply line interrupted
Main switch faulty (if installed)
Additional supply line fuse has blown
(if installed)
Ambient temperature too high
Insufficient ventilation
Condenser is dirty
Defective compressor
Possible cause
Ambient temperature too high
Insufficient ventilation
Condenser is dirty
Faulty fan
Battery capacity exhausted
Troubleshooting
Remedy
Establish a connection
Replace the main switch
Replace the supply line
fuse
Move the refrigerator to
another location
Clean the condenser
Contact customer service
Remedy
Move the refrigerator to
another location
Clean the condenser
Replace the fan
Charge the battery
35