REFRIGERANT AND DRAIN PIPING

4 REFRIGERANT AND DRAIN PIPING
4.1 GENERAL
INCORRECT
CORRECT
Y(*)
!
C A U T I O N
Do not create an upper-slope or rise for the drain piping, since drain
water will flow back to the unit and leakage to the room will occur
when the unit operation is stopped.
Do not connect the drain pipe with sanitary or sewage piping or any
other drainage piping.
4.2 REFRIGERANT PIPING AND DRAINING CONNECTION
The location of Liquid, Gas and the Drain Pipe connection is
shown below.
Liquid Pipe
Gas Pipe
Wiring
holes
Liquid Pipe
Gas Pipe
6
PMML0323A rev.5 - 05/2016
Incorrect:
Upward
Slope
Incorrect:
Drain Piping
Rising Part
connection
1/25~1/100
Down Slope
Drain
trap
X
Common Drain Piping
(mm)
Drain
Pipe
When the common drain piping is connected with other indoor units,
the connected position of each indoor unit must be higher than the
common piping. The pipe size of the common drain pipe must be
large enough according to the unit size and number of unit.
Drain piping will require insulating if the drain is installed in a location
where condensation forming on the outside of drain pipe may drop
and cause damage. The insulation for the drain pipe must be selected
to insure vapor sealing and prevent condensation forming.
Drain trap should be installed next to indoor unit. This trap must be
designed to good practice and be checked with water (charged) and
tested for correct flow. Do not tie or clamp the drain pipe and refriger-
ant pipe together.
?
N O T E
(*)Y distance must be higher than X.
Install drainage in accordance with national and local codes.
After performing drain piping work and electrical wiring, check to
ensure that water flows smoothly as in the following procedure:

Checking Unit without drain-up mechanism
-
Pour approximately 1.8 liters of water into the drain pan
(in each unit).
-
Check to ensure that the water flows smoothly or whether
no water leakage occurs. When water cannot be found
at the end of the drain piping, pour another approximately
1.8 liters of water into the drain pan of each unit.
?
N O T E
Pay attention to the thickness of the insulation when the left side piping is
performed. If it is too thick, piping can not be installed in the unit.
Model
RPI-16.0FSN3PE(-f)
Gas Piping
Ø19.05 (3/4")
Liquid Piping
Ø9.52 (3/8")
mm (in)
RPI-20.0FSN3PE(-f)
Ø22.2 (7/8")
Ø9.52 (3/8")