2 INSTALLATION

The CFW900 frequency inverter must be installed according to the instructions of its user's manual.
ATTENTION!
CFW900 must be installed in an environment with pollution degree 2, as per
IEC 61800-5-1, where condensation must not originate conduction through
the accumulated residues. If the installation site does not meet the pollution
degree requirements, CFW900 must have an ingress protection of at least IP54,
as per IEC 60529, provided either by its enclosure or by an external cabinet.

2.1 STO9 CONNECTIONS

The functional safety signals must be connected to connector XC2 of the CFW900 (connector
related to STO90). The location of this connector, as well as the location of connector XC1 and
DIP switches S1 and S2, is indicated in
R
Power
S
Supply
T
Disconnect
Switch
Figure 2.1: Location of connector XC1, XC2 and DIP switches S1 and S2
Table 2.1 on page 13
describes the safety signals on connector XC2.
Pin
Name
1
GNDS
2
VINS
3
SP2
4
STO2
5
SP1
6
STO1
Figure 2.1 on page
XC1
XC2
S2
PE R S
T
U V W PE
Fuses
Table 2.1: Safety signals on XC2
Reference for the +24 Vdc power supply of the STO90
Input for the +24 Vdc power supply of the STO90
Supply for the STO2 input (dry-contact mode)
Safety input 2
Supply for the STO1 input (dry-contact mode)
Safety input 1