Safety Stop Function

2 INSTALLATION

XC25 Terminals
1
STO1
2
GND1
3
STO2
4
GND2
NOTE!
Both input circuits (for K1 and K2) are electrically isolated from each other. XC25:2
and XC25:4 terminals are not connected internally to inverter +24 V power supply
reference. In most of cases, those terminals are connected to XC1:11 control terminal
in CFW-11 and CFW-11M inverters and to XC1:36 in CFW70X inverters.
NOTE!
Follow the instructions provided on Chapter 3 INSTALLATION AND CONNECTION
of User's Manual.
For XC25 control cabling consider the following:
Use wire gauge from 0.5 mm
torque of maximum 0.50 N.m (4.50 lbf.in).
Use shielded cables connected to ground only on inverter side (use the provided metallic
pieces as shown on
Run the cables separated from the remaining circuits (power, 110 V/220 Vac control, etc.).
It is recommended not to exceed 30 m of cable length.
10 | CFW-11, CFW-11M, CFW70X
Table 2: XC25 terminals (safety stop terminals) signals
Function
Terminal 1 of
safety relay K1 coil
Terminal 2 of
safety relay K1 coil
Terminal 1 of
safety relay K2 coil
Terminal 2 of
safety relay K2 coil
(20 AWG) to 1.5 mm
2
Figure 3 on page
11).
Specifications
Coil rated voltage: 24 V, range: 20...30 Vdc
Coil resistance: 960 Ω ± 10 % @ 20 °C (68 °F)
Coil rated voltage: 24 V, range: 20...30 Vdc
Coil resistance: 960 Ω ± 10 % @ 20 °C (68 °F)
(14 AWG) and maximum tightening
2