Do not operate a meter with an open or incorrect-
ly closed battery (accumulator) compartment or
power it from other sources than those specified
in the present manual.
The meter's inputs are electronically protected
from power surge up to 660 V for 30 seconds.
Repairs may be realised solely by an authorised
service point.
WARNING
Before each use, thoroughly inspect the in-
sulation of the device, checking its wires
for any damage (e.g. cracks, cuts, changes
in structure or color). In case of discover-
ing any faults, do not use the device and
contact the service center.
The device complies with the following standards:
EN 61010-1, EN 61557-1 and EN 61557-2.
NOTE!
Voltage exceeding 600 V connected to the me-
ter may result in its damage.
1.1

Safety symbols

This symbol located near another symbol
or terminal, indicates that the user should
read the further information contained in
the manual.
This symbol located near the terminal,
indicates that in normal use there is a
possibility of dangerous voltages.
Protection class II - double insulation.
This symbol indicates that the device must
not be disposed of into any household
waste containers, but must be provided to
a designated collection point for electronic
waste.
The device meets the legal requirements
of the European Union.
Measurement categories according to IEC 61010-2-
030:
CAT II – concerns measurements performed in
circuits directly connected to low voltage installa-
tions,
CAT III – concerns measurements performed in
buildings installations,
CAT IV – concerns measurements performed at
the source of low voltage installation.